| 输出 | DRP-24V120W1C口N | DRP-24V240W1C口N | DRP-24V480W1C口N | |
| 输出电压 | 24 V | 24 V | 24 V | |
| 输出电压范围 | 24-28 V | 24-28 V | 24-28 V | |
| 输出电流 | 0-5.0 A | 0-10.0 A | 0-20.0 A | |
| 输出功率 | 120 W | 240 W | 480 W | |
| 纹波电压 (20 MHz) | < 100 mVpp | |||
| 保持时间 | 115 VAC | > 20 ms | > 15 ms | |
| 230 VAC | ||||
| 输入 | ||||
| 输入相数 | 单相 | |||
| 输入电压范围 | DRP-24V□W1CAN: 88-264 VAC DRP-24V□W1CBN: 88-264 VAC (直流输入范围 88-375 VDC) 1 |
|||
| 输入频率 | 47-63 Hz | |||
| 输入电流 | 115 VAC | < 1.4 A | < 2.6 A | < 5.0 A |
| 230 VAC | < 0.7 A | < 1.3 A | < 2.5 A | |
| 满载效率 2)(100% 负载) | 115 VAC | > 89.5% | > 91.0% | > 92.0% |
| 230 VAC | > 91.0% | > 93.0% | ||
| 浪涌电流(冷启动) | 115 VAC | < 35 A | < 33 A | < 40 A |
| 230 VAC | < 70 A | < 65 A | < 80 A | |
| 功率因素 | 115 VAC | > 0.96 | > 0.99 | |
| 230 VAC | > 0.93 | > 0.93 | > 0.95 | |
| 漏电流(264 VAC, 50 Hz) | TT/TN | < 0.47 mA | < 0.74 mA | < 1.12 mA |
| IT | < 1.20 mA | < 2.00 mA | < 2.55 mA | |
| 机构 | ||||
| 外壳 / 底架 | 铝质 | |||
| 尺寸(H × W × D) | mm | 124 × 40 × 117 | 124 × 60 × 117 | 124 × 82 × 127 |
| inch | 4.88 × 1.57 × 4.61 | 4.88 × 2.36 × 4.61 | 4.88 × 3.23 × 5.00 | |
| 重量 | kg | 0.58 | 0.84 | 1.2 |
| lb | 1.28 | 1.85 | 2.65 | |
| 冷却方式 | 自然对流 | |||
| 平均故障间隔时间 | > 1,411,300 hrs | > 1,366,200 hrs | > 1,041,600 hrs | |
| 环境 | ||||
| 运行温度 | -25°C 至 +70°C | |||
| 储存温度 | -40°C 至 +85°C | |||
| 运行湿度 | 5 至 95% RH (无冷凝) | |||
| 运行海拔高度 | 0 至 5,000 m (0 至 16,400 ft) | |||